Specifications
				
					Input
- Nominal 220VAC (range 198VAC-256VAC), 50/60Hz, 1.5A.
 - Input fuse rated @ 5A/250V.
 
Output
- 12VDC or 24VDC selectable output.
 - 6A continuous supply current.
 - Filtered and electronically regulated output.
 - Short circuit and thermal overload protection.
 
Battery Charging
- Built-in charger for sealed lead acid or gel type batteries.
 - Automatic switch over to stand-by battery when AC fails.
 - Zero voltage drop when switched over to battery backup.
 - (Batteries are sold separately).
 
Supervision
- AC fail supervision (form "C" contacts).
 - Notification trigger is selectable for 30 seconds (factory set) or 6 hours.
 - Low battery supervision (form "C" contacts).
 - Battery presence supervision (form "C" contacts).
 
Visual Indicators
- AC input, DC output and BAT trouble.
 
Electrical
Temperature:
- Operating: 0° C to 49° C (32° F to 120° F).
 - Storage: - 20° C to 70° C ( - 4° F to 158° F).
 
- Relative Humidity: 85%  +/- 5%.
 BTU/Hr. (approx.):
- 12VDC: 37 BTU/Hr.
 - 24VDC: 74 BTU/Hr.
 
- System AC input VA requirement: 330VA.
 
				 
					 
		
			
												
				Dimensions & Weight
				
					
											Dimensions (approximate):
						
							- 4.5"W x 7.8"L x 2.6"H (114.3 mm W x 198.12 mm L x 66.04 mm H).
 
						
										
					
					Weights (approximate):
						
							- Product Weigtht: 1.55 Lbs. (0.7 kg).
 
							- Shipping Weigtht: 1.75 Lbs. (0.79 kg).